Thermally Tested and Certified
ModuSec has been independently tested
by the UK insurance industry’s Loss Prevention Council and
achieved BS476 F90 standard – suitable for high-risk areas.
Now also tested to Lloyds IMO A60 Standard (tested
at a higher pressure with multiple pipe/cable entry points –
for marine applications).
Tested to over 1000°C at the Building Research
Establishment -according to BS476 pt22 at 30 minutes: No discernable
rise at the unexposed face (800°C outside). At 60 minutes: Mean
temperature of just 40°C at the unexposedface (950°C outside)
– well below the critical level for hardware and media. The
test continued to achieve an F90 rating: 93 minutes insulation plus
98 minutes integrity media corrupts at 55°C -hardware is damaged
above 70°C |